surge arrester t63 - c350xs 3 - electrode - arrester ordering code: b88069x8050b102 ab e / ab pm issue 01, 17.01.2003 page 1 of 2 dc spark - over voltage 1) 2) 4 ) 300 ... 500 v impulse spark - over voltage 4 ) at 100 v/s - for 99 % of measured values - typical values of distribution at 1 kv/s - for 99 % of measured values - typical values of distribution < 800 < 700 < 900 < 80 0 v v v v nominal impulse discharge current (wave 8/20 s) 5 ) single impulse discharge current (wave 8/20 s) 5 ) 20 30 ka ka nominal alternating discharge current (50 hz, 1 s) 5 ) alternating discharge current (50 hz, 9 cycles) 5 ) 20 130 a a service l ife 5 400 operations 10/1000 s 1000 a insulation resistance at 100 v dc 4 ) > 10 g w capacitance at 1 mhz 4 ) < 1.5 pf transverse delay time 3 ) < 0.2 s arc voltage at 1 a glow to arc transition current glow voltage ~ 35 ~ 1 ~ 200 v a v weight ~ 4 g operation and storage temperature - 40 ... +90 c climatic category (iec 60068 - 1) 40/ 90/ 21 marking, blue 350 yy o 350 - nominal voltage yy - year of production o - non radioactive 1) at delivery aql 0.65 level ii, din iso 2859 2) i n ionized mode 3 ) test according to itu - t rec. k.12 4 ) tip or ring electrode to center electrode 5 ) total current through center electrode, half value through tip respectively ring electrode. terms in accordance with itu - t rec. k.12 and din 57845/vde0845
surge arrester t63 - c350xs 3 - electrode - arrester ordering code: b88069x8050b102 epcos ag 2002. reproduction, publication and dissemination of this data sheet, enclosures hereto and the information contained therein without epcos' prior express conse nt is prohibited. purchase orders are subject to the general conditions for the supply of products and services of the electrical and electronics industry recommended by the zvei (german electrical and electronic manufacturers' associ a tion), unless otherwi se agreed. ab e / ab pm issue 01, 17.01.2003 page 2 of 2 not to scale dimensions in mm non controlled document
|